Event List (690343)

System Date/Time FracSec Event Event Subtype Category Area Node Unit Module Module Desc Attribute State Event Level Desc 1 Desc 2
SHP Office DeltaV 2023-01-24 13:33:29 1884 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 13:33:29 2375 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 13:33:29 9395 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-24 13:33:29 9397 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 13:33:28 5901 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 13:33:26 1882 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 13:33:26 2376 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 13:33:26 9391 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-24 13:33:26 9397 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 13:33:25 5897 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 12:56:04 2037 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 12:56:04 2534 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 12:56:04 9546 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-24 12:56:04 9548 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 12:56:03 6051 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 12:56:01 2038 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 12:56:01 2531 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 12:56:01 9553 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-24 12:56:01 9559 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-24 12:56:00 6050 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2023-01-24 04:31:57 2348 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2023-01-24 04:31:52 859 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-24 04:31:32 872 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-24 04:31:21 5473 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2023-01-24 04:10:21 5095 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2023-01-24 04:10:12 741 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-24 04:09:52 747 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-24 04:09:45 8135 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Office DeltaV 2023-01-23 17:56:51 4062 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 17:56:51 4063 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:56:50 566 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:56:50 6552 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:56:50 7045 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:56:49 4056 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 17:56:49 4063 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:56:48 569 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:56:48 6551 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:56:48 7047 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:40:21 4129 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 17:40:21 4130 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:40:20 636 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:40:20 6616 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:40:20 7109 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:40:18 4126 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 17:40:18 4132 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:40:17 634 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:40:17 6616 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:40:17 7109 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:36:32 4153 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 17:36:32 4154 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:36:31 647 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:36:31 6634 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:36:31 7128 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:36:30 4144 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 17:36:30 4150 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:36:29 649 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:36:29 6636 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 17:36:29 7130 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2023-01-23 15:24:56 6295 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2023-01-23 15:24:51 5967 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-23 15:24:31 5964 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-23 15:24:21 5963 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Standby Unavailable
SHP Unit DeltaV 2023-01-23 15:24:01 5964 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-23 15:23:57 2058 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Unit DeltaV 2023-01-23 14:43:40 6180 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2023-01-23 14:43:31 5686 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-23 14:43:11 5681 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-23 14:43:04 9070 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Office DeltaV 2023-01-23 13:37:59 5129 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 13:37:59 5130 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:58 1634 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:58 7620 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:58 8112 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:55 5123 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 13:37:55 5129 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:54 1631 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:54 7617 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:54 8112 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:48 5129 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 13:37:48 5131 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:47 1634 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:47 7618 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:47 8114 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:43 5126 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 13:37:43 5132 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:42 1634 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:42 7620 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:37:42 8113 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:33:16 5150 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 13:33:16 5152 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:33:15 1655 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:33:15 7640 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:33:15 8134 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:33:14 5149 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 13:33:14 5155 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:33:13 1657 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:33:13 7642 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:33:13 8135 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:32:12 5162 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 13:32:12 5164 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:32:11 1658 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:32:11 7644 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:32:11 8139 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:32:06 5152 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 13:32:06 5159 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:32:05 1657 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:32:05 7645 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 13:32:05 8140 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:56:53 5296 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:56:53 5298 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:56:52 1799 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:56:52 7786 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:56:52 8278 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:56:51 5289 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:56:51 5295 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:56:50 1799 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:56:50 7784 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:56:50 8281 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2023-01-23 12:47:11 4185 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2023-01-23 12:47:01 4972 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-23 12:46:41 4963 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-23 12:46:35 5452 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Office DeltaV 2023-01-23 12:39:11 5345 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:39:11 5346 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:39:10 1852 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:39:10 7839 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:39:10 8330 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:39:09 5342 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:39:09 5349 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:39:08 1850 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:39:08 7839 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:39:08 8333 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:38:14 5376 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:38:14 5378 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:38:13 1877 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:38:13 7864 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:38:13 8354 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:38:11 5365 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:38:11 5372 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:38:10 1877 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:38:10 7863 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:38:10 8354 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:40 5404 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:30:40 5405 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:39 1910 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:39 7894 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:39 8387 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:38 5405 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:30:38 5411 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:37 1910 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:37 7895 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:37 8386 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:17 5408 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:30:17 5409 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:16 1910 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:16 7896 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:16 8388 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:13 5399 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:30:13 5405 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:12 1907 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:12 7894 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:30:12 8389 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:36 5407 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:29:36 5409 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:35 1908 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:35 7895 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:35 8389 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:31 5398 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:29:31 5404 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:30 1906 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:30 7893 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:30 8387 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:24 5401 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:29:24 5403 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:23 1903 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:23 7890 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:23 8385 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:10 5394 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:29:10 5401 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:09 1901 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:09 7887 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:29:09 8381 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:26:11 5385 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:26:11 5387 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:26:10 1893 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:26:10 7879 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:26:10 8372 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:26:08 5388 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:26:08 5394 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:26:07 1896 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:26:07 7882 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:26:07 8374 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:24:50 5424 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:24:50 5425 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:24:49 1927 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:24:49 7914 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:24:49 8406 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:24:47 5423 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:24:47 5430 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:24:46 1928 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:24:46 7915 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:24:46 8406 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:23:08 5435 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:23:08 5437 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:23:07 1935 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:23:07 7922 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:23:07 8414 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:23:05 5426 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:23:05 5433 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:23:04 1935 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:23:04 7923 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:23:04 8414 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:21:41 5429 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:21:41 5430 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:21:40 1934 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:21:40 7920 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:21:40 8411 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:21:38 5428 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:21:38 5434 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:21:37 1934 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:21:37 7921 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:21:37 8415 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:20:39 5427 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:20:39 5429 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:20:38 1932 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:20:38 7921 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:20:38 8415 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:20:36 5426 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:20:36 5434 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:20:35 1932 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:20:35 7919 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:20:35 8412 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:19:11 5445 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:19:11 5446 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:19:10 1951 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:19:10 7937 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:19:10 8429 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:19:04 5447 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:19:04 5455 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:19:03 1954 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:19:03 7938 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:19:03 8432 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:51 5449 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:18:51 5451 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:50 1954 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:50 7942 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:50 8437 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:43 5445 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:18:43 5452 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:42 1953 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:42 7940 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:42 8434 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:35 5449 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:18:35 5451 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:34 1957 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:34 7941 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:34 8432 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:32 5454 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:18:32 5461 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:31 1954 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:31 7941 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:31 8432 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:11 5443 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:18:11 5444 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:10 1947 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:10 7933 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:10 8425 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:08 5439 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:18:08 5446 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:07 1946 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:07 7932 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:18:07 8424 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:46 5437 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:17:46 5438 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:45 1938 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:45 7925 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:45 8419 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:44 5433 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:17:44 5439 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:43 1940 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:43 7927 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:43 8419 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:13 5436 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:17:13 5437 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:12 1944 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:12 7927 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:12 8421 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:09 5434 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:17:09 5442 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:08 1944 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:08 7929 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:17:08 8423 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:15:20 5467 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:15:20 5468 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:15:19 1974 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:15:19 7956 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:15:19 8447 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:15:16 5464 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:15:16 5471 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:15:15 1967 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:15:15 7954 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:15:15 8448 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:14:21 5467 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:14:21 5468 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:14:20 1969 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:14:20 7955 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:14:20 8451 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:14:17 5464 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:14:17 5470 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:14:16 1972 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:14:16 7958 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:14:16 8449 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:13:20 5463 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:13:20 5465 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:13:19 1968 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:13:19 7954 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:13:19 8446 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:13:16 5459 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:13:16 5466 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:13:15 1965 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:13:15 7952 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:13:15 8446 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:10:27 5482 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:10:27 5484 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:10:26 1985 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:10:26 7972 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:10:26 8467 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:10:23 5478 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:10:23 5484 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:10:22 1987 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:10:22 7974 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:10:22 8465 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:08:15 5483 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:08:15 5484 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:08:14 1987 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:08:14 7974 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:08:14 8471 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:08:10 5482 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:08:10 5490 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:08:09 1989 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:08:09 7975 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:08:09 8468 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:06:36 5485 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:06:36 5486 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:06:35 1989 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:06:35 7973 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:06:35 8469 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:06:32 5490 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:06:32 5496 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:06:31 1991 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:06:31 7978 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:06:31 8470 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:04:16 5506 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:04:16 5508 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:04:15 2005 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:04:15 7992 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:04:15 8485 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:04:13 5497 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:04:13 5503 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:04:12 2005 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:04:12 7992 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:04:12 8485 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:03:59 5500 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:03:59 5502 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:03:58 2010 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:03:58 7994 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:03:58 8486 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:03:55 5497 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:03:55 5503 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:03:54 2005 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:03:54 7992 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:03:54 8486 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:02:24 5518 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:02:24 5520 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:02:23 2017 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:02:23 8005 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:02:23 8501 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:02:17 5514 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:02:17 5521 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:02:16 2020 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:02:16 8007 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:02:16 8499 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:54 5518 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:01:54 5519 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:53 2021 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:53 8006 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:53 8501 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:50 5515 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:01:50 5521 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:49 2021 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:49 8008 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:49 8500 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:18 5518 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 12:01:18 5519 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:17 2023 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:17 8007 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:17 8502 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:15 5511 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 12:01:15 5517 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:14 2021 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:14 8007 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 12:01:14 8500 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:58 5541 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 11:56:58 5543 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:57 2043 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:57 8028 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:57 8522 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:55 5532 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 11:56:55 5539 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:54 2040 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:54 8028 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:54 8521 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:18 5545 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 11:56:18 5546 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:17 2043 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:17 8029 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:17 8523 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:15 5535 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 11:56:15 5541 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:14 2042 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:14 8029 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:14 8525 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:03 5538 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 11:56:03 5539 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:02 2043 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:02 8029 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:02 8524 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:56:00 5537 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 11:56:00 5543 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:55:59 2044 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:55:59 8031 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 11:55:59 8523 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:55:35 5783 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 10:55:35 5784 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:55:34 2287 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:55:34 8274 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:55:34 8768 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:55:32 5788 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 10:55:32 5795 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:55:31 2286 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:55:31 8274 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:55:31 8765 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:25:33 5891 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 10:25:33 5893 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:25:32 2396 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:25:32 8384 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:25:32 8877 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:25:30 5891 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 10:25:30 5897 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:25:29 2396 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:25:29 8384 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 10:25:29 8877 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:30:26 6133 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 09:30:26 6134 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:30:25 2632 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:30:25 8619 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:30:25 9114 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:30:23 6124 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 09:30:23 6130 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:30:22 2633 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:30:22 8619 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:30:22 9114 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Unit DeltaV 2023-01-23 09:26:00 947 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Available
SHP Unit DeltaV 2023-01-23 09:25:51 3682 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM INACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-23 09:25:31 3673 ALARM HARDWARE AREA_A CNTR01 CNTR01 Rig Controller MAINT_ALM ACT/UNACK 11-WARNING MAINT Redundancy: Not Communicating - Standby
SHP Unit DeltaV 2023-01-23 09:25:24 4162 EVENT SYSTEM AREA_A CNTR01 REDU 00-80-74-01-83-6E Standby is now Unavailable
SHP Office DeltaV 2023-01-23 09:00:59 6238 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 09:00:59 6240 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:00:58 2742 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:00:58 8725 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:00:58 9219 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:00:56 6235 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 09:00:56 6241 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:00:55 2738 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:00:55 8723 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 09:00:55 9219 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:30:42 6358 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 08:30:42 6360 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:30:41 2856 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:30:41 8839 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:30:41 9333 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:30:39 6344 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 08:30:39 6350 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:30:38 2852 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:30:38 8839 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:30:38 9334 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:29:37 6344 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 08:29:37 6345 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:29:36 2847 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:29:36 8833 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:29:36 9326 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:29:30 6339 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO ANALOG2/AI1/ALM1 I/O Input Failure
SHP Office DeltaV 2023-01-23 08:29:30 6346 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:29:29 2846 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:29:29 8831 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:29:29 9325 ALARM INSTRUMENT BOILER CNTRL01 PC_DI2 Phoenix Contact Digital in 1 PV_BAD ACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:29:11 6348 EVENT PROCESS BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 ACTIVE 4-INFO Error Cleared I/O Input Failure
SHP Office DeltaV 2023-01-23 08:29:11 6349 ALARM INSTRUMENT BOILER CNTRL01 ANALOG2 Phoenix Contact Analogue 1 PVBAD_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:29:10 2852 ALARM INSTRUMENT BOILER CNTRL01 BUS_COUPLER_01 Phoenix Contact Remote IO FAULT_ALM INACT/UNACK 15-CRITICAL IOF General I/O Failure
SHP Office DeltaV 2023-01-23 08:29:10 8838 ALARM INSTRUMENT BOILER CNTRL01 PC_DI1 Phoenix Contact Digital in 1 PV_BAD INACT/UNACK 15-CRITICAL IOF General I/O Failure