| System | Date/Time | FracSec | Event | Event Subtype | Category | Area | Node | Unit | Module | Module Desc | Attribute | State | Event Level | Desc 1 | Desc 2 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SHP Office DeltaV | 2023-02-26 10:29:34 | 5701 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:29:33 | 2202 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:29:33 | 8189 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:29:33 | 8681 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:29:12 | 5700 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:29:12 | 5702 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:29:11 | 2204 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:29:11 | 8189 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:29:11 | 8683 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:29:09 | 5697 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:29:09 | 5703 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:29:08 | 2203 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:29:08 | 8189 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:29:08 | 8683 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:29:00 | 5700 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:29:00 | 5701 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:59 | 2207 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:59 | 8191 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:59 | 8684 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:56 | 5700 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:28:56 | 5706 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:55 | 2206 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:55 | 8192 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:55 | 8688 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:19 | 5722 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:28:19 | 5723 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:18 | 2224 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:18 | 8209 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:18 | 8701 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:14 | 5713 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:28:14 | 5719 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:13 | 2221 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:13 | 8208 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:28:13 | 8704 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:27:31 | 5745 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:27:31 | 5747 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:27:30 | 2234 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:27:30 | 8220 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:27:30 | 8712 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:27:28 | 5726 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:27:28 | 5732 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:27:27 | 2238 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:27:27 | 8221 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:27:27 | 8713 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:23:02 | 5777 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:23:02 | 5778 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:23:01 | 2284 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:23:01 | 8268 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:23:01 | 8765 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:22:55 | 5779 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:22:55 | 5785 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:22:54 | 2284 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:22:54 | 8272 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:22:54 | 8763 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:22:17 | 5794 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:22:17 | 5795 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:22:16 | 2291 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:22:16 | 8279 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:22:16 | 8775 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:22:15 | 5787 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:22:15 | 5793 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:22:14 | 2292 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:22:14 | 8279 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:22:14 | 8772 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:20:06 | 5804 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:20:06 | 5806 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:20:05 | 2304 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:20:05 | 8290 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:20:05 | 8784 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:20:03 | 5797 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:20:03 | 5804 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:20:02 | 2302 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:20:02 | 8289 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:20:02 | 8783 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:56 | 5803 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:19:56 | 5804 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:55 | 2302 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:55 | 8289 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:55 | 8784 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:53 | 5797 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:19:53 | 5803 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:52 | 2303 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:52 | 8289 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:52 | 8784 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:28 | 5809 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:19:28 | 5810 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:27 | 2314 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:27 | 8297 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:27 | 8789 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:25 | 5806 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:19:25 | 5812 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:24 | 2314 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:24 | 8298 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:24 | 8789 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:02 | 5809 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:19:02 | 5810 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:01 | 2316 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:01 | 8303 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:19:01 | 8795 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:18:59 | 5807 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:18:59 | 5814 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:18:58 | 2314 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:18:58 | 8301 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:18:58 | 8795 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:18:19 | 5825 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:18:19 | 5826 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:18:18 | 2325 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:18:18 | 8311 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:18:18 | 8803 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:18:15 | 5819 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:18:15 | 5826 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:18:14 | 2324 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:18:14 | 8310 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:18:14 | 8804 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:16:17 | 5824 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:16:17 | 5825 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:16:16 | 2325 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:16:16 | 8312 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:16:16 | 8808 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:16:13 | 5822 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:16:13 | 5828 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:16:12 | 2330 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:16:12 | 8314 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:16:12 | 8805 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:14:02 | 5869 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:14:02 | 5871 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:14:01 | 2374 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:14:01 | 8360 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:14:01 | 8855 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:58 | 5869 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:13:58 | 5875 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:57 | 2376 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:57 | 8363 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:57 | 8856 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:47 | 5873 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:13:47 | 5874 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:46 | 2374 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:46 | 8361 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:46 | 8856 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:45 | 5869 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:13:45 | 5875 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:44 | 2375 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:44 | 8362 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:44 | 8855 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:17 | 5877 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:13:17 | 5879 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:16 | 2375 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:16 | 8362 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:16 | 8859 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:15 | 5870 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:13:15 | 5877 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:14 | 2375 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:14 | 8363 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:13:14 | 8856 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:59 | 5859 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:10:59 | 5860 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:58 | 2360 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:58 | 8348 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:58 | 8842 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:57 | 5856 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:10:57 | 5862 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:56 | 2361 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:56 | 8347 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:56 | 8840 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:42 | 5857 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:10:42 | 5859 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:41 | 2362 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:41 | 8348 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:41 | 8842 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:35 | 5857 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:10:35 | 5865 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:34 | 2364 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:34 | 8349 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:10:34 | 8845 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:09:22 | 5861 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:09:22 | 5863 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:09:21 | 2365 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:09:21 | 8352 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:09:21 | 8843 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:09:19 | 5859 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:09:19 | 5865 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:09:18 | 2364 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:09:18 | 8351 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:09:18 | 8842 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:08:42 | 5848 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:08:42 | 5850 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:08:41 | 2356 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:08:41 | 8338 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:08:41 | 8832 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:08:38 | 5842 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:08:38 | 5849 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:08:37 | 2349 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:08:37 | 8336 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:08:37 | 8832 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:07:45 | 5831 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:07:45 | 5833 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:07:44 | 2333 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:07:44 | 8320 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:07:44 | 8812 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:07:41 | 5836 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:07:41 | 5842 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:07:40 | 2330 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:07:40 | 8317 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:07:40 | 8813 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:07:01 | 5822 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:07:01 | 5823 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:07:00 | 2310 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:07:00 | 8298 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:07:00 | 8789 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:06:59 | 5802 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:06:59 | 5811 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:06:58 | 2311 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:06:58 | 8294 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:06:58 | 8790 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:06:29 | 5791 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:06:29 | 5793 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:06:28 | 2293 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:06:28 | 8279 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:06:28 | 8774 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:06:24 | 5781 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:06:24 | 5788 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:06:23 | 2291 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:06:23 | 8276 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:06:23 | 8769 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:49 | 5774 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:05:49 | 5775 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:48 | 2275 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:48 | 8262 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:48 | 8754 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:43 | 5767 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:05:43 | 5774 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:42 | 2272 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:42 | 8260 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:42 | 8751 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:07 | 5749 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:05:07 | 5751 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:06 | 2248 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:06 | 8235 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:06 | 8727 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:03 | 5740 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:05:03 | 5746 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:02 | 2242 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:02 | 8231 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:05:02 | 8724 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:03:15 | 5660 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:03:15 | 5662 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:03:14 | 2161 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:03:14 | 8147 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:03:14 | 8641 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:03:11 | 5664 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:03:11 | 5670 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:03:10 | 2161 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:03:10 | 8146 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:03:10 | 8640 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:00:49 | 5546 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:00:49 | 5547 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:00:48 | 2049 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:00:48 | 8034 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:00:48 | 8525 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:00:45 | 5536 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 10:00:45 | 5543 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:00:44 | 2043 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:00:44 | 8027 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 10:00:44 | 8521 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:59:18 | 5434 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:59:18 | 5436 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:59:17 | 1939 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:59:17 | 7924 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:59:17 | 8418 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:59:16 | 5432 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:59:16 | 5439 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:59:15 | 1938 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:59:15 | 7925 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:59:15 | 8417 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:58:36 | 5409 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:58:36 | 5410 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:58:35 | 1912 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:58:35 | 7897 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:58:35 | 8390 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:58:34 | 5403 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:58:34 | 5409 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:58:33 | 1910 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:58:33 | 7899 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:58:33 | 8389 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:56:29 | 5346 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:56:29 | 5347 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:56:28 | 1842 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:56:28 | 7830 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:56:28 | 8325 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:56:27 | 5338 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:56:27 | 5344 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:56:26 | 1843 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:56:26 | 7830 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:56:26 | 8322 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:55:53 | 5330 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:55:53 | 5332 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:55:52 | 1831 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:55:52 | 7818 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:55:52 | 8313 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:55:50 | 5322 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:55:50 | 5329 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:55:49 | 1832 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:55:49 | 7816 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:55:49 | 8312 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:54:37 | 5300 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:54:37 | 5302 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:54:36 | 1802 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:54:36 | 7788 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:54:36 | 8280 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:54:32 | 5292 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:54:32 | 5298 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:54:31 | 1800 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:54:31 | 7786 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:54:31 | 8282 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:51:40 | 5336 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:51:40 | 5337 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:51:39 | 1841 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:51:39 | 7828 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:51:39 | 8319 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:51:31 | 5353 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:51:31 | 5359 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:51:30 | 1844 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:51:30 | 7830 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:51:30 | 8321 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:50:05 | 5344 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:50:05 | 5345 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:50:04 | 1842 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:50:04 | 7829 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:50:04 | 8325 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:50:03 | 5338 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:50:03 | 5345 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:50:02 | 1842 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:50:02 | 7829 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:50:02 | 8323 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:47:31 | 5380 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:47:31 | 5382 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:47:30 | 1869 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:47:30 | 7855 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:47:30 | 8347 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:47:28 | 5361 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:47:28 | 5367 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:47:27 | 1868 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:47:27 | 7855 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:47:27 | 8347 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:46:55 | 5382 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:46:55 | 5384 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:46:54 | 1884 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:46:54 | 7871 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:46:54 | 8362 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:46:51 | 5387 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:46:51 | 5394 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:46:50 | 1883 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:46:50 | 7870 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:46:50 | 8363 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:54 | 5408 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:44:54 | 5409 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:53 | 1914 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:53 | 7899 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:53 | 8391 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:52 | 5403 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:44:52 | 5410 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:51 | 1914 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:51 | 7899 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:51 | 8392 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:38 | 5410 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:44:38 | 5412 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:37 | 1915 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:37 | 7901 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:37 | 8394 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:34 | 5408 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:44:34 | 5414 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:33 | 1918 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:33 | 7904 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:44:33 | 8399 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:40:29 | 5439 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:40:29 | 5441 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:40:28 | 1939 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:40:28 | 7925 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:40:28 | 8421 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:40:27 | 5434 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:40:27 | 5440 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:40:26 | 1940 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:40:26 | 7926 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:40:26 | 8419 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:39:35 | 5447 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:39:35 | 5449 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:39:34 | 1949 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:39:34 | 7935 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:39:34 | 8431 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:39:32 | 5441 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:39:32 | 5447 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:39:31 | 1951 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:39:31 | 7936 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:39:31 | 8431 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:38:37 | 5459 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:38:37 | 5460 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:38:36 | 1960 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:38:36 | 7947 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:38:36 | 8438 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:38:33 | 5452 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:38:33 | 5458 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:38:32 | 1957 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:38:32 | 7944 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:38:32 | 8437 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:32:57 | 5529 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:32:57 | 5531 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:32:56 | 2031 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:32:56 | 8020 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:32:56 | 8512 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:32:55 | 5528 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:32:55 | 5536 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:32:54 | 2037 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:32:54 | 8020 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:32:54 | 8514 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:31:24 | 5535 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:31:24 | 5537 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:31:23 | 2037 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:31:23 | 8024 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:31:23 | 8517 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:31:22 | 5530 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:31:22 | 5537 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:31:21 | 2041 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:31:21 | 8027 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:31:21 | 8516 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:30:49 | 5534 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:30:49 | 5536 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:30:48 | 2036 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:30:48 | 8023 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:30:48 | 8514 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:30:39 | 5529 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:30:39 | 5535 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:30:38 | 2034 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:30:38 | 8021 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:30:38 | 8514 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:28:28 | 5574 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:28:28 | 5576 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:28:27 | 2084 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:28:27 | 8066 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:28:27 | 8557 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:28:25 | 5574 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:28:25 | 5581 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:28:24 | 2081 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:28:24 | 8068 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:28:24 | 8558 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:27:26 | 5591 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:27:26 | 5593 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:27:25 | 2094 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:27:25 | 8080 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:27:25 | 8576 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:27:23 | 5588 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:27:23 | 5594 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:27:22 | 2094 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:27:22 | 8079 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:27:22 | 8575 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:26:09 | 5602 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:26:09 | 5604 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:26:08 | 2106 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:26:08 | 8090 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:26:08 | 8584 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:26:05 | 5599 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:26:05 | 5607 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:26:04 | 2104 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:26:04 | 8091 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:26:04 | 8586 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:25:50 | 5602 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:25:50 | 5604 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:25:49 | 2110 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:25:49 | 8093 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:25:49 | 8588 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:25:40 | 5604 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:25:40 | 5611 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:25:39 | 2108 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:25:39 | 8097 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:25:39 | 8589 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:24:32 | 5616 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:24:32 | 5617 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:24:31 | 2122 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:24:31 | 8107 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:24:31 | 8604 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:24:29 | 5616 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:24:29 | 5622 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:24:28 | 2123 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:24:28 | 8109 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:24:28 | 8604 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:23:57 | 5622 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:23:57 | 5624 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:23:56 | 2124 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:23:56 | 8111 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:23:56 | 8604 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:23:51 | 5624 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:23:51 | 5630 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:23:50 | 2123 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:23:50 | 8108 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:23:50 | 8601 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | ACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:21:10 | 5635 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | Error Cleared | I/O Input Failure | |||
| SHP Office DeltaV | 2023-02-26 09:21:10 | 5636 | ALARM | INSTRUMENT | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | PVBAD_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:21:09 | 2139 | ALARM | INSTRUMENT | BOILER | CNTRL01 | BUS_COUPLER_01 | Phoenix Contact Remote IO | FAULT_ALM | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:21:09 | 8125 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI1 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:21:09 | 8617 | ALARM | INSTRUMENT | BOILER | CNTRL01 | PC_DI2 | Phoenix Contact Digital in 1 | PV_BAD | INACT/UNACK | 15-CRITICAL | IOF | General I/O Failure | ||
| SHP Office DeltaV | 2023-02-26 09:21:07 | 5633 | EVENT | PROCESS | BOILER | CNTRL01 | ANALOG2 | Phoenix Contact Analogue 1 | ACTIVE | 4-INFO | ANALOG2/AI1/ALM1 | I/O Input Failure |